LB-CUSTOM-EV Load Bank

Eagle Eye’s LB-CUSTOM-EV series of customized DC load banks feature unique design and excellent performance. There are a number of non-constant current discharge models to cover a wide voltage range and a current up to 2000A. While primarily for testing EV charger capacity, these load banks can also be used across a wide range of applications, including telecom, power utility, data center, forklift and others. Users can easily control via manual local push button, circuit breaker or PC remote control.

Benefits

  • State-of-the-Art Design: Rugged construction with a user-friendly control panel.
  • Versatile Application: Ideal for DC load tests where constant current discharge is not required.
  • Customizable Power Control: Sectionalized control allows for tailored load step and time settings.
  • Real-Time Monitoring: LCD meter displays test current, voltage, power, and time in real-time.
  • Flexible Control Modes: Operate via circuit breaker, local push button, or PC control.
  • Comprehensive Protection: Features over-voltage and over-temperature protection, along with an emergency stop button.
  • Advanced Load Element: Utilizes the latest high-density power load element for enhanced safety and durability.
  • Efficient Ventilation: Axial flow fans provide quick ventilation with low noise.
  • Custom Models Available: Various voltage and current models can be customized upon request.

Own a device that needs service or annual calibration?

Submit an RMA >

Visit Eagle Eye University for information on our battery training courses.

 

Specifications

Rated Voltage3 phase 4 wire 400-440Vac, 50Hz
Input Rated Power3 phase 4 wire 30-40KW
Power Step1KW, 2KW, 2KW, 5KW, 10KW, 10KW, 10KW, 20KW
3 phase synchronized control. All steps could
be combined arbitrarily.
Power Factor1
Power Range1KW-30KW adjustable
Load Accuracy±5%
Way of DisplayReal time display of voltage, current,
power, frequency and other parameters
Way of WiringL1, L2, L3 & N
Power SupplySingle phase AC230V/50Hz
Working ModeCould work continuously
ProtectionEmergent stop button, over temperature alarm and over temperature/over voltage protection
Dimensions L x W x HApp. 24 x 30 x 31.5-40 in (600 x 750 x 800-1000 mm)
WeightApp. 155-176 lbs (70-80 kg)
Operation Temperature-10℃~+50℃
Humidity5%~90% Relative humidity
IP RatingIP20 for indoor use
Insulation ClassF
Way of Control Mode
(3 Options)
Standard: Local manual control with circuit breakers or push buttons
Optional: Control via local touch screen tablet
Optional: PC software remote control with RS485 connection with load bank
Fans Noise75db
CoolingForced air cooling, air inlets from bottom and outlet to the top
Power FactorSingle phase AC230V/50Hz
Standard PartsLoad bank, AC power cord and RS485-USB cable (if with PC remote control)
Optional parts: load cable with customized length
Altitude≤2500 meters
Mobility4 rolling wheel
 