Specifications
Type of Input Power | 115 VAC 50/60 Hz |
---|
Rated Capacity at 100% Duty Cycle: | 300 Amperes at 30 VAC/VDC |
---|
Rated Capacity at 30% Duty Cycle: | 350 Amperes at 35 VAC/VDC. 12.25 kW |
---|
Dimensions | 19.25 x 20.625 x 11.25 in (489 x 524 x 286 mm) |
---|
Weight | 44 lbs (20 kg) |
---|
Load Accuracy (per gear) | ±5% |
---|
Cooling | Forced air cooling, side air in, side air out |
---|
Operating Environment | Operating Temperature: 5 – 122 °F (-15 – 50 °C) Humidity: ≤95% RH |
---|
FAQs
What are some common applications areas for this product?
Common applications include but are not limited to:
- DC Generator Systems
- DC Battery Systems
- UPS Testing
- Rectifiers
- Power Supply
- Power Converter Units
- Standby Generators
- Diesel and Gas Turbines
- Micro-turbines
- Wind Generators
- Solar Arrays
- Electrical Distribution Systems
- Circuit Breakers
- Other Electrical and DC Power Supply Testing
Are the LB-Series constant current load banks compatible with online applications?
Yes, the constant current load bank could be used in an online application however we do not recommend this practice unless testing the performance of the charger / rectifier as discharging the batteries while connected to a load source leaves the batteries vulnerable for system failure.
What is meant by constant current?
Constant current means that the load bank will deliver a constant load set by the user from the beginning to end of a load test regardless of the drop in voltage.
What safety cutoffs do the LB-Series Constant Current load banks have?
The DC load bank will shut down based on user adjustable settings of time, string voltage, and capacity. It also has thermal protection shutdown.
Is the load bank able to discharge strings in parallel?
As long as the nominal voltage falls within the working voltage of the specific unit the load tester will be able to discharge parallel strings.