Eagle Eye Power Solutions
1-877-805-3377

Constant Current DC Battery Load Banks with Wireless Cell Monitoring

Eagle Eye’s SLB-Series DC load banks are designed for user ease of use, portability, and versatility in mind. Discharge testing batteries is the only verifiable method the capacity of your batteries and the SLB delivers a programmable, constant current load for your testing needs. Whether you are load testing for capacity, performance, acceptance, NERC compliance, or other, the SLB provides an economical complete package solution. Increase employee and battery system safety with PER CELL monitoring and standard built in auto-shutdown features. To suit a variety of industries and diverse applications, Eagle Eye offers over 75 standard models to fit your exact needs at the best price.

Benefits

  • Safely monitor live tests remotely with wireless communication to the SLB load bank
  • DataView software includes live monitoring, data recording, and report exporting to Microsoft Excel
  • Discharge auto-shutdown for time duration, total string voltage, capacity, and individual cell voltage
  • Parallel with another SLB-Series unit for increased discharge current capacity
  • Assistant discharge feature allows for compatibility with existing non-SLB load banks
  • Increase current and add individual cell monitoring to your existing equipment with SLB-Series
  • Built-in circuit breakers for emergency shutdown and overload protection
  • Optional: Real-time display of voltage for each cell/unit with DAC package for 1.2V, 2V, 6V, 12V cells
  • Optional: Custom DAC packages available for monitoring of uncommon cell voltages and configurations
 

Specifications

Cell VoltageStandard DAC: 1.2V1, 2V, 6V, 12V / Optional 3.6V, 4V, and other custom DAC configurations available upon request
Discharge Current RangeSingle Load: 12 – 600A / Parallel Load: Up to 1200A
Discharge Voltage RangeRange: 10 – 576V (Max) / Voltage Steps: 12V, 24V, 36V, 48V, 80V, 125V, 240V, 380V, 480V
AccuracyDischarge Current: 1% / Voltage: 0.5% – 0.8%
ResolutionDischarge Current: 0.1 A or 0.5% / Voltage: 0.001 V
Sampling Interval5 seconds – 1 minute
Data TransferUSB, Wireless (466 MHz)
DisplayBacklit LCD
Operating Environment0 – 40 °C (32 – 104 °F)
Power Requirements110/220 VAC 50/60 Hz / DC (from connected batteries)
DimensionsSmall: 400 x 177 x 288 mm (15.7 x 7 x 11.3 in)
Medium: 520 x 202 x 355 mm (20.5 x 8 x 14 in)
Large: 555 x 225 x 435 mm (22.5 x 8.9 x 17.2 in)
X-Large: 603 x 400 x 740 mm (23.7 x 15.7 x 29 in)
XX-Large: 762 x 406 x 737 mm (30 x 16 x 29 in)
WeightSmall: 11 kg (24 lbs) Medium: 16 kg (36 lbs) Large: 21 kg (47 lbs) X-Large: 42 kg (93 lbs) XX-Large: 55 kg (122 lbs)
 

FAQs

What are some common applications areas for this product?

Common applications include but are not limited to:

  • DC Generator Systems
  • DC Battery Systems
  • UPS Testing
  • Rectifiers
  • Power Supply
  • Power Converter Units
  • Standby Generators
  • Diesel and Gas Turbines
  • Micro-turbines
  • Wind Generators
  • Solar Arrays
  • Electrical Distribution Systems
  • Circuit Breakers
  • Other Electrical and DC Power Supply Testing

Does the SLB-Series come with software?

Each SLB comes standard with Dataview software. This software allows us to live monitor, view test data, and export reports to Microsoft Excel

How is cell voltage monitoring accomplished?

The SLB-Series utilizes DACs (data acquisition cases) to connect to each cell. The DAC includes a wiring harness that connects to the cells. Each DAC communicates back to the SLB load bank wirelessly.

What is the power requirement for the SLB?

The exact power consumption of an SLB varies with model and discharge current, however expect the draw to be less than 9A at max current. A 15A circuit breaker is sufficient for power needs

Product Training

If you would like product specific training, please contact Eagle Eye directly. We offer complimentary training over the phone. Quotes can be provided for on site product-training. For more information call 1-877-805-3377 or email us at info@eepowersolutions.com. We provide timely support for all inquiries.

EEU Training Courses

Eagle Eye University (EEU) provides scheduled courses tailored to specific aspects of the critical power industry. All courses are also available at your location. The following courses are applicable to Constant Current DC Battery Load Banks with Wireless Cell Monitoring.

Battery 101
Март 2, 2020 - Март 3, 2020

A comprehensive overview of battery types and how they are used in Standby Power applications

Battery Discharge Testing & Analysis
Сентябрь 14, 2020 - Сентябрь 15, 2020

Outline steps required to prepare and carryout a discharge test in accordance with IEEE recommended practices

PRC-005-6 Battery Operation & Maintenance Compliance