This horn/strobe combo emits high-quality signals intended for use in cUL general signaling applications. The xenon beacons with horns are bright, low current, high decibel, combination signals designed for use where a distinctive visual or audible signal is required. The strobes flash at 1fps across their full operating voltage range.
The strobe and horn can be operated independently. It can be flush mounted, designed to mount in a standard 4″ (102mm) square electrical box with extension ring (total min. depth of 3″ (75mm) not supplied.)
Key Features
- Flash rate 60 fpm
- 100 dB at 1 meter/90 dB at 10 ft (measured in anechoic chamber)
- Low current draw
- Terminals for easy wiring
- Gray, engineered thermoplastic housing
- Outdoor-rated models available upon request
Specifications
Operating Voltage* | 24 VAC 50/60 Hz; 24 VDC |
Operating Current, Horn** | 72 mA; 22mA |
Operating Current, Strobe** | 390 mA; 390 mA |
Flash Rate (per second) | Approximately 1 fps |
Sound Level Output at 10 ft. (3.05m) anechoic chamber | 90 dBA nominal |
Operating Environment | Indoor: 93% at 90°F (32°C) relative humidity; 32 to 120°F (0 to 49°C) variable ambient temperature. Outdoor: 98% at 104°F (40°C) relative humidity; -31 to 150°F (-35°F to 66°C) variable ambient temperature. |
**Horn and strobe currents are additive when connected in parallel.
Resources & Support
FAQs
What is the Eagle Eye Power Solutions HS-2000 used for?
The HS-2000 is a flush-mount horn and strobe designed to provide clear visual and audible alerts in environments where hydrogen gas detection or other critical alarms are required.
Where is the HS-2000 typically installed?
Can the HS-2000 be triggered by Eagle Eye Power Solutions H₂ Hydrogen Gas Detectors?
What are the power requirements for the HS-2000?
The HS-2000 typically operates on 24VDC power, but specific voltage requirements should be confirmed on the product datasheet to match your application.
Is the strobe light customizable (color or flash rate)?
The standard strobe is red, but alternate colors and flash rates may be available depending on your application or safety code requirements. Contact Eagle Eye Power Solutions for customization options.
Is the Eagle Eye Power Solutions HS-2000 rated for hazardous environments?
While the HS-2000 is designed for industrial safety use, it is not rated as intrinsically safe on its own. It is used in conjunction with intrinsically safe devices (like the HGD-4000) in monitored environments.
How loud is the HS-2000 audible alarm?
The horn produces a high-decibel tone, typically 85–100 dB depending on the mounting and enclosure. This ensures it can be heard clearly over ambient industrial noise.
Can multiple HS-2000 units be networked or triggered at once?
Yes, multiple HS-2000 units can be connected to the same detector output or control panel to provide coverage across larger rooms or facilities.
Request Quote
Complete Your DC Power Solution
PRC-005-6 Battery Operation & Maintenance Compliance
Get trained by industry experts on how battery monitoring can help you meet and maintain compliance with NERC PRC-005-6.
Gas Ventilation Systems
Explore the VS-Series ventilation systems for battery rooms and confined spaces with flammable gases. Available in two sizes, featuring mechanical louvers and integration with hydrogen gas detectors for automatic operation.

Battery Signage
Enhance battery room safety with compliant signage to prevent accidents and meet OSHA requirements with six essential safety signs.