HGD-5000 H2 Hydrogen Gas Detector

In Stock

The HGD-5000 Hydrogen Gas Detector will monitor hydrogen gas buildup in storage rooms and facilities that house batteries. The detector provides terminal block connections for single-phase 110 AC, 24VAC or 18-60VDC power. Detected Hydrogen levels are displayed in % Vol and traffic light indication – Green (Normal) Yellow (Warning) Alarm (Red). The control relays are used to switch an exhaust fan and warning alarms, the detector also provides analog outputs that can be connected directly to the fan speed controller to regulate the fan speed. If the concentration of hydrogen gas detected reaches 1% Vol the screen will display yellow, and the warning relay will close activating the ventilation fan. If the concentration reaches 2% the screen will display red, and the alarm relay and an 80 dB internal warning will sound.

Benefits

  • Replaceable sensor with a long life
  • 110AC, 24V AC, 18-60VDC power supply
  • 2* Internal relays for fan/alarm activation
  • 2* Analog outputs
  • Output to external strobe
  • 4-sec alarm delay to prevent false activation
  • Supplied calibrated

Own a device that needs service or annual calibration?

Submit an RMA >

Visit Eagle Eye University for information on our battery training courses.

 

Specifications

Target GasHydrogen 1% Vol (warning) 2% Vol (Alarm)
Alarm Relay(2) Internal relays, (2) Analog outputs
Mounting(4) #4 POZI screws
Operating EnvironmentTemperature: -10 – 40 °C (14 – 104 °F)
Power Requirements110 VAC, 24VAC, 18~60VDC
Dimensions151 x 111 x 50 mm (5.95 x 4.37 x 1.97 in)
ComplianceIEEE Standard 450; National Fire Protection Agency (NFPA) Article 64; NFPA 2: Hydrogen Technologies Code; Uniform Building Code (UBC) Section 6400; National Electric Code (NEC) Section 480.9 (A); NEC 501.125 (B); NEC 501.105 (1)-3 – use in Class 1 Division 2 Group B.
Housing MaterialABS PA765. Flame Retardant UL 94V-1
Indicator / Display1.8″ TFT
Weight7.5 oz
End-of-life Years10
Warranty3 year
 

Downloads

Product Literature

Support Documents

Technical Information

FAQs

What regulations apply to battery charging areas?
OSHA Regulations (Standards – 29 CFR), National Electrical Code (National Fire Protection Association Standard NFPA 70), and associated directives, interpretations and compliance letters apply. For the latest information, see the web sites of OSHA (osha.gov) and NFPA (nfpa.org). Other regulations, state and local, may also apply.

What do these regulations require?
To the best of our knowledge at the time of this posting, existing regulations require that:

  • Provisions be made for sufficient diffusion and ventilation of gases from storage batteries to prevent the accumulation of explosive mixtures.
  • Adequate ventilation means providing natural or mechanical dilution sufficient to limit the accumulation of hydrogen gas in air at the charging site to levels below the lower explosive limit of 4.1%.
  • A typical exhaust fan can meet this requirement if it is used in such manner that the concentration of hydrogen gas in the fan’s ambient air never exceeds the lower explosive limit.

What can cause a hydrogen gas explosion?
Hydrogen gas, 4.1% or more mixed with air, can be ignited by a flame, spark, or static electricity.

Can the detector itself cause an explosion?
Not if you make tight wire connections to the detector. The only moving parts are in the internal relays, and the relays are hermetically sealed.

Will the detector work in a non-oxygen environment?
No. The sensor requires an oxygen environment.

Does the detector detect or react to other gasses?
The sensor detects several other combustible gases in addition to hydrogen — ethanol, isobutane, methane, propane. Its sensitivity to these other gasses, however, is much lower than its sensitivity to hydrogen. This should not noticeably affect its operation.

What is the detector operating temperature?
The detector operating temperature is 14 to 104 degrees F, ( -10 to 40 degrees C).

What is the response time?
When power is first applied, or after a power interruption, approximately 10 minutes will elapse before the detector starts to function. This delay is to prevent false activation. After this delay, response time to hydrogen for the first (1%) relay is about 4 seconds; response time for the second (2%) relay and/or alarm is 3 seconds later (total: about 7 seconds).

Does the detector have a built-in warning alarm?
The detector has a built-in 80 db warning alarm that activates at a 2% concentration of hydrogen.

Where should I place the hydrogen gas detector?
Install the detector at the highest, draft-free location in the battery compartment or room where hydrogen gas might accumulate.

How do I install the detector?
The detector is designed to attach directly to a wall or ceiling, or to a conduit box, using four screws. You will need to run power and relay wires to the detector, plus a modular cable to the optional remote, if used.

How is the detector powered?
Normal power is 115 volts 50/60 Hz AC. If specified at time of order, the detector can be customized for 220 volts 50/60 Hz AC, or for 24, 36 or 48 volts DC.

How much power does the detector consume?
The detector consumes 80 ma, 170 ma if the buzzer is sounding.

How large an exhaust fan can the detector control?
The internal relay dry-contacts are rated at 10 amps / 250 vac, sufficient for most 1/3 HP fans. For higher current requirements, add an external relay.

How many detectors do I need?
Similar to smoke detectors, hydrogen detectors sense hydrogen only at the sensor, not at a distance. How many detectors you need depends upon where hydrogen might accumulate near your ceiling. Factors affecting this are: a. Room size. b. Type of ceiling — flat, pitched, compartmented, etc. c. Natural air flow patterns. If unsure, add one or more detectors to be safe.

Can one detector control more than one sensor?
No. The detector can operate only one sensor.

Can the sensor be remotely mounted from the detector?
Normally, no. The sensor is mounted on a small board inside the detector. For special OEM requirements, some modifications can be made. Consult Eagle Eye.

How can I be sure the detector is working?
Each detector has a test button. Push and hold the test button for ten seconds. The LED’s will light in sequence, the relay(s) will close to operate whatever is connected, and the warning buzzer will sound. This test can also be run from the optional remote, if used. This procedure will test the detector’s electronics, but not the sensor itself. There is no way accurately to test the sensor in the field. If you have hydrogen in a tank, you can fill a balloon with hydrogen and release it at the sensor to see the reaction. Do not use hydrogen sulfide – it can damage the sensor. For a more accurate test, you can purchase test gas from a gas supplier and flood the sensor with it, but these concentrations are very small and may not give a correct result. Fortunately, when the sensor fails, often due to contamination, it normally becomes more sensitive, falsely activating the relay and/or alarm.

How does the detector connect to the optional remote box?
The remote box connects to the detector box via a standard style 6-connector, 6-contact telephone-type modular cable.

How long will the sensor last?
Normal sensor life is over 10 years. For safety sake we suggest you replace it every 10 years.

How can I replace the sensor?
To replace the sensor, order a new sensor board from your dealer or Eagle Eye. Remove the cover of the detector. Pull out the old sensor board and insert the new board. Replace the cover. Run the push-to-test-button procedure. That’s all there is to it.

What is the warranty?
Hydrogen gas detectors are warranted to be free of defects in workmanship and material for a period of 3 years from the date of purchase.

Where can I buy an Eagle Eye HGD-5000?
You can buy a detector directly from Eagle Eye Power Solutions, LLC.

What is the recommended wiring gauge for installing the HGD-5000?
You should consult your electrician or an engineer for the proper wire gauge for your application. You will want a wire gauge that is sufficient for carrying the appropriate load from your circuit breaker which may vary in size based on 120/220 VAC and your specific application.