Centroid Snet 2 Software Updates

The below outlines the latest software versions for the BMS-Series battery monitoring systems. New updates will be added as they become available. For the latest VIGILANT® Battery Monitoring System update, please visit VIGILANT® Software Update.

The Centroid Snet software package applies to the BQMS, iPQMS, BDS-Pro, and BMS-icom systems. The initial installation requires support programs that are not available to download on this page. Please contact Eagle Eye if you are installing the program for the first time.

Update Instructions

The following update instructions apply to all versions. Please note that example screenshots may show a different version that what is shown on your version.

Step 1: Stop the Centroid Snet 2 Service


  • Close Centroid Viewer. Open the Run command (Win key + R) and type “services.msc”.
Windows Run dialog box with "services.msc" typed in the Open field, used to access the Services management console in Windows.
  • In Services, select CentroidSnet 2 and then click Stop on the left.
Windows Services management console showing the "Centroid Snet2" service selected and running with an automatic startup type.

Step 2: Uninstall Centroid Snet 2 and Centroid Viewer


  • Open Programs and Features from the Control Panel or Add/Remove Programs and uninstall Centroid Snet2 and Centroid Viewer.
Windows "Uninstall or Change a Program" window showing Centroid Snet2 and Centroid Viewer version 1.6.9.4 installed by Waton Co., Ltd., with options to uninstall or change the programs.

Step 3: Install New Version of Centroid Snet 2 & Centroid Viewer


  • Execute Centroid Snet2 v2.x.x.exe, be sure to “Run as administrator.”
Windows File Explorer showing installation files for Centroid Snet2 v2.0.1, CentroidViewer v2.0.1, MariaDB 10.0.19, and MySQL Connector Net 6.9.8, including file types, modification dates, and sizes.
  • Progress through the install. On the last screen, make sure “Run Centroid Snet2 2.x.x” is checked, then click finish.
Centroid Snet2 2.0.1 Setup Wizard completion screen showing successful installation with the option to run the program selected and the "Finish" button highlighted.

NOTE: A message may appear that says “Centroid Snet 2 has stopped working”. If this occurs, just click Cancel. The program will still be installed correctly.

  • Execute CentroidViewer v2.x.x.exe.
File explorer view showing installation files for CentroidViewer v2.0.1, Centroid Snet2 v2.0.1, along with MariaDB and MySQL Connector installers.
  • Follow the prompts to complete the installation, the checkbox to run the program does not need to be checked.
  • Open the Services window and start the Centroid Snet 2 service.
Windows Services window showing the Centroid Snet2 service with automatic startup type and option to start the service, running under Local System account.
Windows Services panel showing Centroid Snet2 service actively running with automatic startup type under the Local System account, with options to stop or restart the service.
  • With the service running, open Centroid Viewer, all of the registered systems should be online and the measurement data history should be present.
Centroid Viewer interface displaying the Local Server dashboard with a list of registered devices, including IPGMS, BDS_PRO, and BQMS, all showing online status. Eagle Eye Power Solutions logo is visible in the upper right corner.

Downloads

Latest Version: 2.4.33 (19.1 MB zip file)

Released: Aug 8, 2021

Centroid Snet 2 Changelog