VS-24 Hydrogen Gas Ventilation System

    Battery Room Ventilation and Exhaust Systems

    Eagle Eye Power Solutions hydrogen gas ventilation system parts with large silver fan and vent
    Eagle Eye Power Solutions VS-12 wall unit ventilation system: four small fans encased behind a metal screen

    Time for a Tune-up?

    If your device needs service or annual calibration let us help.

    The VS-24 Hydrogen Gas Ventilation System is a forced ventilation fan system used in battery charging rooms and other areas where hydrogen may be present. This is to be used in conjunction with the HGD-2000 and HGD-3000 Hydrogen Gas Detectors. The hydrogen gas detector is mounted in the highest part of the room and the VS-24 vent fan is mounted through the outside wall.

    The system has four fans factory-rated at 850 CFM each. This conforms to N+1 for 2550 CFM. The vent is equipped with a “Positive Airflow Shut Off” feature. These doors can be closed by an external electric command, and will stop any airflow from passing through the fans. The VS-24 is primarily set up to exhaust air but can be reversed to source forced air into a room.

    Key Features

    • Compliance with IEEE Std 450
    • Compliance with National Fire Protection Agency (NFPA) Article 64
    • Compliance with Uniform Building Code (UBC) Section 6400
    • Automatic Operation and Continuous 24/7 Monitoring
    • High Sensitivity and Stability
    • Long Life-Span for Reliable Monitoring
    • 20-gauge galvanized steel
    • Inexpensive protection for equipment and personnel
    • Two-Year Warranty

    Specifications

    ConnectionsInput: Positive shutoff control, N.O. Dry Contacts
    Output: 1% Fan Running, 2% Alarm, N.O. Dry Contacts
    Mounting(4) 38 mm (1.5 in) Standard 607 mm (24 in)
    Positive Shut-OffDry contact activated, manually reset
    DimensionsH x W x D: 610 x 610 x 450 mm (24 x 24 x 18 in)
    WeightFan: 23 kg (51 lbs)
    Rain Shield & Damper: 10.9 kg (24 lbs)
    Safety Standard(4) fans rated at 850 CFM Total 3400 CFM
    N+1 (3) Fans at 850 CFM Total 2550 CFM for 777 sq. m (2550 sq. ft)
    OptionsMounting wing placement, room exhaust source, small or large rain
    shield, N.O. to N.C., custom features on request
    CertificationsClass 1 Division 2 Group B motor

    FAQs

    What are the benefits of installing a VS-24 ventilation system?

    What are the power requirements for the VS-24?

    Can I connect multiple ventilation systems to a single hydrogen gas detector?

    Can the ventilation system be set up in the reverse direction (forcing air inside)?

    Why must the Positive Airflow Shut Off be manually reset?

    Are the conductors between the VS-24 and HGD-2000/HGD-3000 considered power limited circuits?

    Does the VS-24 have control relays and what do they consist of if so?

    Am I able to run duct from the ventilation system?

    Request Quote

    To top