VIGILANT™ Software Update

Introduction

The VIGILANT Battery Monitoring system receives periodic updates which can be installed by the end user. Updates are installed on the VIGILANT Monitor via the Web-Interface. As of version 1.3.11, each system must be updated directly on the web-interface sequentially. This means if updating from 1.3.8 to 1.3.11, you must first update from 1.3.8 through 1.3.10 first.

Eagle Eye Power Solutions also offers a service to perform updates. If interested, please request a quote.

Update Instructions

Estimated Time Required: 00:10:00 – 00:45:00

The following update instructions apply to all versions since 1.3.7. Please note that example screenshots may show a different version that what is shown on your version.

Step 1: Confirm Current Version


  • Prior to obtaining the update file(s), the current software version must be verified to ensure the correct update file is used.
  • Login to the VIGILANT web-interface and open the Settings page by clicking Settings on the web-interface header.
  • On the lower left under the buttons, check to confirm the current software version as shown below.

Step 2: Download Update File(s)


  • The most recent update files will generally be available on this page under the Downloads section.

NOTE: Updates must be done sequentially, you cannot skip versions. For example, if updating from 1.3.8 to 1.3.10, you must first update from 1.3.8 to 1.3.9.

  • Click the version needed to expand its contents. A download link will be available as well as the release date and major changelog details. Download the update file to an easily accessible location (e.g., Downloads folder).
  • After downloading the update zip file, do not extract it. The entire zip file will be uploaded to the web-interface.

Step 3: Upload Update File


  • Navigate to the Update page which is accessed differently depending on the current software version:
    • For versions 1.3.9 or later: On the Settings page, click the Actions button then click the Update button.
    • For versions prior to 1.3.9: In the web-browser URL bar, type the following after the IP address /settings/update/
  • When the update page loads, the following information may be present:
    • System version: Should match the version shown on the Settings page.
    • Newest stable version: If the VIGILANT has connection to the internet, it will clarify what the newest stable version is (e.g., 1.3.10)
    • Available space: The available space left of the SSD.

NOTE: The page might display a message that “System timed out trying to reach DNS server”. This will occur if the system is not connected to a DNS, it does not affect the update procedure.

  • On the Update page, click the Browse… button and select the update zip file (note, the zip file extension may not be visible on all computers. The file should be located wherever it was saved previously (e.g., Downloads folder).
  • After selecting the file, it should show the correct version next to the Browse… button. If so, click the Upload button to start the update.
  • When the upload starts, it will progress through 14 stages automatically. The progress of these stages will be shown as a blue notification bar on the top of the page.
  • When the update is completed, the notification bar will turn green and confirm the update was completed successfully.
  • After the update is complete, be sure to reboot the monitor from the Settings/Actions/Reboot/ page.
  • Should the update fail for any reason, please Contact Us directly.

Downloads

Click the version below to reveal download link and changelog information. The latest complete changelog for all versions can be downloaded.

Version 1.3.11 (latest version)

Version 1.3.10

Version 1.3.9

Version 1.3.8 (oldest available)